欧美黑人乱大交_中文无码日韩欧免费视频_日本va欧美va精品发布_玩弄丰满少妇xxxxx性多毛_熟妇人妻无乱码中文字幕

網(wǎng)站首頁(yè)

/

產(chǎn)品展示
FF 018 21m3h to 102m3h

產(chǎn)品名稱:

FF 018 21m3h to 102m3h

產(chǎn)品簡(jiǎn)介:

詳細(xì)信息
Axial fan, ball bearing service life 50,000h at +25°C (+77°F), 65% RH fan body aluminium, rotor plastic
Connection 2 wires with pressure clamps 2.5mm2, length 100mm
Casing (filter fan and exit filter) plastic according to UL94 V-0, light grey
Hood (filter fan and exit filter) plastic according to UL94 V-0, light grey;weather proof and UV light resistant according to UL746C (f1)
Mounting frame with double-sided industrial adhesive band for fixing to the outside of enclosure; certain operating circumstances can make the additional use of screws necessary (see drilling template); a template for the enclosure cut-out is included in the delivery of the filter fans
Filter mat M5 acc. to DIN EN 779, filtering degree 94%
Filter material synthetic fibre with progressive construction, temperature resistant to +100°C, self-extinguishing class F1,moisture resistant to 100% RH, reusable - cleaning by washing or vacuuming
Operating/Storage temperature s-10 to +70°C (+14 to +158°F) / -40 to +70°C (-40 to +158°F)
Operating/Storage humidity max. 90% RH (non-condensing)
Protection type/Protection class I
Approvals UL File No. E234324, EAC, VDE only: 230V

Special features

Theself-adhesive sealof the mounting frame prevents dust and water from entering the cabinet.

Functional designof the intake and exit fan hoods very effectively prevents direct intrusion of falling water and dust. The advantage is that the filter mat does not get so quickly contaminated with dirt and thus does not need to be exchangedso often

Theair channelingmakes the filter fan particularly quiet in operation

Functional andmodern designenables time-saving assembly and maintenance.

Thedirection of air flow can easily be switchedby reversing the axial fan (sizes 1 to 3).

EMC versions and other voltages on request

Art. No. Operating voltage Air volume, free flow Air volume with exit filter Current con- sumption Power con- sumption Average noise level (DIN EN ISO 4871) Depth in enclosure Enclosure cut-out Weight (approx.) Protection type
01800.0-00 230VAC, 50Hz 21m3/h 16m3/h 80mA 15W 31dB (A) 45mm 97 x 97mm + 0.4 0.6Kg IP54
01801.0-00 230VAC, 50Hz 55m3/h 42m3/h 100mA 15W 40dB (A) 58mm 125 x 125mm + 0.4 1.0Kg IP54/IP551
01802.0-00 230VAC, 50H 102m3/h 68m3/h 100mA 15W 39dB (A) 86mm 176 x 176mm + 0.4 1.3Kg IP54/IP551
01800.0-01 120VAC, 60Hz 24m3/h 18m3/h 160mA 15W 31dB (A) 45mm 97 x 97mm + 0.4 0.6Kg IP54/IP551
01801.0-01 120VAC, 60Hz 63m3/h 48m3/h 180mA 15W 40dB (A) 58mm 125 x 125mm + 0.4 1.0Kg IP54/IP551
01802.0-01 120VAC, 60Hz 117m3/h 78m3/h 180mA 15W 39dB (A) 86mm 176 x 176mm + 0.4 1.3Kg IP54/IP551

1Using fine filter mats type F5/M5 increases the protection type to IP55, but reduces the air volume

Time-saving assembly and maintenance

STEGO′s filter fans are easily installed by one personfrom outsidethe cabinet.

1.) Make cut-out in the cabinet wall. The cut edge of the cabinet opening should be free of dirt, filings and grease. A template for the enclosure cut-out is included in the delivery of the filter fan. 2.) Remove protective film from the sealing strips on the mounting frame. Press mounting frame into the cabinet opening. The frame stays permanently in the cabinet. (For size 176mm and up we recommend additional screw fixing.) 3.) Electrically connect the axial fan using the clip connectors. Push the unit into the mounting frame. Fix using screws. 4.) Insert the filter mat in the hood. Clip on. Finished. Changing the filter mat or fan is quickly done by one person. To change the filter mat simply remove the filter hood, insert the new mat and snap the hood back again. No tools required. Maintenance of the fan can easily be done without removing the mounting frame

EXIT FILTER EF 118

Art. No. Depth in enclosure Air volume, free flow Weight (approx.) Filter mat Protection type
11800.0-00 16mm 97 x 97mm + 0.4 0.3kg G4 acc. to DIN EN 779, filtering degree 94% IP54
11801.0-00 16mm 125 x 125mm + 0.4 0.4kg G4 acc. to DIN EN 779, filtering degree 94% IP54/IP551
11802.0-00 16mm 176 x 176mm + 0.4 0.6kg G4 acc. to DIN EN 779, filtering degree 94% IP54/IP551

EXIT FILTER EF 118

1Using fine filter mats type F5/M5 increases the protection type to IP55, but reduces the air volume

FILTER MAT FM 086/FFM 086

Filter mat 79 x 79mm 118 x 118mm 168 x 168mm
G4 (1 packaging unit = 3 pcs.) Art. No. 08600.0-00 Art. No. 08601.0-00 Art. No. 08602.0-00
F5/M5 (1 packaging unit = 3 pcs.) - Art. No. 08604.0-00 Art. No. 08605.0-00

IP55, but reduces the air volume


版權(quán)所有:大連保稅區(qū)宇洋貿(mào)易有限公司 備案號(hào):遼ICP備05011078號(hào)

技術(shù)支持:銘科網(wǎng)絡(luò)